What glass can a commercial skylight use?

The building code allows laminated glass with at least a 30 mil interlayer, wired glass, heat strengthened or fully tempered glass, or approved light transmitting plastic. Every layer of a multiple layer unit must come from that list, and tempered, heat strengthened or wired glass as the bottom layer needs a broken glass screen, with some exceptions.

What the code says

The International Building Code covers this in sections 2405.2 to 2405.4 of chapter 24.

  • Single layer: laminated with a 30 mil interlayer, wired, heat strengthened, fully tempered or approved plastic.
  • Multiple layers: each layer from the same list.
  • Screens: not needed under laminated glass or plastic.
  • Curb: 4 inches above the roof for skylights under 45 degrees from horizontal.

Annealed glass is allowed only under the narrow exceptions in the screening section.

Frames and roof loads

The frame has to resist the roof loads in the structural chapter, and in the two most fire resistant construction types it must be noncombustible. Skylights under 45 degrees can’t sit flat in the plane of the roof, except on home roofs pitched 3 in 12 or more. In a corrosive setting, the screen must be a noncorrosive material of equal strength.