How much air can storefront glass leak?

Storefront glazing and curtain walls can leak no more than 0.06 cfm per square foot under the commercial energy code. Windows, sliding doors and swinging doors are allowed 0.20. Each assembly must be tested by an accredited, independent lab and labeled by its maker.

What the rule says

The commercial part of the International Energy Conservation Code covers this in section C402.5.4 and Table C402.5.4 of chapter 4.

  • Storefront glazing: 0.06.
  • Curtain walls: 0.06.
  • Windows and sliding doors: 0.20.
  • Skylights: 0.20, or 0.30 with condensation weep openings.
  • Exceptions: field built assemblies sealed to the air barrier rules, and buildings that pass a whole building air test.

The figures are cfm per square foot of the assembly, at the test pressure set in the standard.

Field built storefront

Storefront assembled on site from framing and glass, rather than shipped as a tested unit, can instead be sealed to the code’s air barrier rules. Either way, gaps at the perimeter and torn gaskets let air through, so check them when glass is replaced.